Description
ALSTOM KCEU142
Alstom KCEU142 is an obsolete numerical protection relay, now under ABB heritage product portfolio. It is specially designed for directional overcurrent and wattmetric sensitive earth fault protection, ideal for isolated or resonant earthed medium voltage networks. It supports IEC and ANSI time‑current curves, fault waveform capture and event logging. The unit provides opto‑isolated binary inputs and freely assignable output contacts, and connects to substation control via RS485 KBus. It remains a critical stocking spare for legacy switchgear protection in power generation and process industry substations.
ALSTOM KCEU142
| Parameter | Specification |
|---|---|
| Product Type | Numerical Directional Overcurrent & Earth Fault Protection Relay |
| Compatible System | Alstom / ABB MiCOM protection family, substation automation system |
| Core Function | Three-stage directional overcurrent, directional sensitive earth fault protection with wattmetric characteristic; fault recording, event logging, configurable time curves, local indication and remote communication for isolated / Petersen coil compensated power networks |
| Signal Type | Rated current: 1 A or 5 A software selectable; rated frequency 50 / 60 Hz; 3 opto‑isolated binary inputs; 4 programmable trip / signal output contacts plus watchdog contact |
| Galvanic Isolation | Galvanic isolation for CT / VT inputs, binary inputs and communication port |
| Power Supply | Multi‑range auxiliary supply: 24–250 V DC, 100–240 V AC |
| Power Consumption | Max 12 W |
| Diagnosis | Power‑on self‑test, CT / VT supervision, contact wear monitoring, watchdog fault detection, event & disturbance record storage |
| Indicator | Power, healthy, trip, fault, communication status LED indicators |
| Communication | RS485 KBus serial interface |
| Hot Swap | Non hot‑swappable; isolate CT circuits and auxiliary supply before replacement |
| Operating Temperature | -25 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 (front panel IP40) |
| Certifications | IEC 60255, CE, UL |
| Mounting | Panel cutout mounting for switchgear protection compartment |
| Application | Power plant, utility substation, industrial medium voltage network, arc‑suppression coil grounded system earth fault and overcurrent protection |
| Remarks | Part No KCEU142, originally Alstom, later inherited by ABB; obsolete numerical protection relay; fully function tested before shipment |

- KCEU142