Description
ABB REM610
ABB REM610 is a dedicated numerical motor protection IED of the Relion 610 family, designed for medium and large low‑voltage motors as well as small‑to‑medium medium‑voltage asynchronous motors. It monitors the whole motor lifecycle including start‑up, steady running, stall and standstill cooling. With the optional RTD module, it directly measures winding and bearing temperatures via RTD or PTC sensors. The withdrawable plug‑in design allows rapid replacement. It supports multi‑protocol communication for SCADA integration and built‑in fault recording for post‑fault analysis. Widely used in petrochemical, mining, water treatment and general process plants for critical motor protection.
ABB REM610
| Parameter | Specification |
|---|---|
| Product Type | Numerical motor protection, measurement and control IED |
| Compatible System | LV / MV asynchronous motor switchgear, industrial and utility substation |
| Rated Frequency | 50 / 60 Hz selectable |
| Rated Current In | 1 A / 5 A |
| Auxiliary Supply | AC: 100~240 V; DC: 24~250 V |
| Power Consumption | < 9 W quiescent, max 13 W operating |
| Core Protection Functions | Thermal overload, motor start-up supervision, stall protection, multi-stage overcurrent, short-circuit protection, undercurrent (loss of load), non-directional earth fault, negative-sequence unbalance, phase reversal, phase discontinuity, breaker failure protection, trip circuit supervision |
| Optional Function | RTD / PTC temperature measurement module, arc flash protection, locked restart inhibition |
| Recording | Disturbance recorder, event recorder, time-stamped fault records, waveform capture |
| Communication Protocols | IEC 61850, IEC 60870-5-103, Modbus, DNP3, SPA, LON, Profibus |
| Local Interface | LCD HMI, front service port, programmable digital inputs and relay output contacts |
| Diagnosis | Continuous self-supervision, trip circuit supervision, watchdog monitoring |
| Mounting | Panel flush / semi-flush mounting, withdrawable plug-in unit |
| Operating Temperature | -25 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non-condensing |
| Protection Class | IP54 for front panel, IP20 for rear compartment |
| Certifications | CE, UL, marine type approval available |
| Application | Pumps, fans, conveyors and compressors; also used for thermal overload protection of distribution transformers and cable feeders |
| Remarks | Obsolete legacy IED, discontinued since 2017, fully calibrated, firmware and function tested before shipment |

- ABB REM610