Description
ABB REU610
ABB REU610 is a dedicated numerical voltage protection IED within the Relion 610 family. It monitors phase and residual voltages for medium‑voltage distribution networks, delivering multi‑stage overvoltage, undervoltage and residual overvoltage protection. It supports automatic busbar changeover and islanding isolation for distributed power sources. The withdrawable plug‑in design simplifies maintenance and replacement. Integrated disturbance recording and multi‑protocol communication enable seamless connection to SCADA systems. Widely deployed in utility substations, industrial switchgear and offshore power systems for voltage supervision and protection.
ABB REU610
| Parameter | Specification |
|---|---|
| Product Type | Numerical voltage protection, measurement and supervision IED |
| Compatible System | Medium voltage switchgear, utility & industrial distribution substation |
| Rated Frequency | 50 / 60 Hz user selectable |
| Rated VT Secondary Voltage | 100 / 110 / 115 / 120 V selectable |
| Auxiliary Supply | AC: 100~240 V; DC: 24~250 V |
| Power Consumption | Less than 9 W quiescent, max 13 W during operation |
| Core Protection Functions | Two-stage overvoltage, two-stage undervoltage, two-stage residual overvoltage, negative sequence overvoltage, positive sequence undervoltage, breaker failure protection, trip circuit supervision |
| Optional Function | Islanding detection, automatic busbar transfer initiation |
| Recording | Disturbance recorder, event recorder, up to 100 time-stamped event records, fault waveform recording up to 80 seconds |
| Communication Protocols | IEC 61850, IEC 60870-5-103, Modbus, DNP3, SPA, LON, Profibus |
| Local Interface | Alphanumeric LCD HMI, front optical SPA port, programmable LEDs, configurable digital inputs and relay outputs |
| Diagnosis | Continuous self-supervision, trip circuit supervision, internal watchdog monitoring |
| Mounting | Panel flush / semi-flush mounting, withdrawable plug-in unit |
| Operating Temperature | -25 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non-condensing |
| Protection Class | IP54 for front panel, IP20 for rear compartment |
| Certifications | CE, UL, marine type approval available |
| Application | Busbar, transformer, capacitor bank and motor voltage supervision, residual voltage based earth fault detection, anti-islanding protection for distributed generation, offshore and industrial power distribution |
| Remarks | Obsolete legacy IED, discontinued from 2017, fully calibrated, firmware and function tested before shipment |

- ABB REU610