Description
GE 269 PLUS-D/O-100P-125V
GE Multilin 269-PLUS-D is a discontinued microprocessor motor management relay serving as the base unit of the 269PLUS series. It supports configurable RTD temperature monitoring for bearings and windings, and provides comprehensive motor protection functions including thermal overload, locked rotor, jam, phase unbalance, single phasing, short circuit and ground fault. It features thermal capacity tracking, anti‑repeated start logic, pre‑trip alarm and fault event logging. Remote communication is realized through RS485 Modbus RTU for parameter configuration and real‑time data acquisition. This relay is a common choice for low and medium voltage three‑phase motors in motor control centers of power plants, petrochemical, water treatment and heavy industrial sites.
GE 269 PLUS-D/O-100P-125V
| Parameter | Specification |
|---|---|
| Product Type | Digital motor management & protection relay |
| Compatible System | GE Multilin 269 Plus motor protection platform |
| Core Function | Motor thermal overload, locked rotor, jam, phase unbalance, single‑phase, short circuit, ground fault protection, temperature monitoring, electrical metering, fault recording and motor control logic |
| Signal Type | CT current sampling, multiple RTD inputs, optically isolated digital inputs, programmable relay outputs, optional analog output |
| Galvanic Isolation | Galvanic isolation for CT, RTD and digital input channels |
| Power Supply | Multiple optional control supply: 120V AC/DC, 240V AC/DC, 24V DC |
| Power Consumption | Max 20 VA, peak inrush up to 65 VA |
| Diagnosis | RTD open / short detection, over‑range alarm, built‑in self‑test, thermal capacity tracking, event recorder, fault waveform capture |
| Indicator | Multi‑function status LEDs, backlit alphanumeric LCD, membrane keypad for local setting and readout |
| Communication | RS485, Modbus RTU protocol; no native Ethernet or fiber port |
| Hot Swap | Non hot‑swappable, panel mounting device |
| Operating Temperature | -20 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 when installed inside control cabinet |
| Certifications | CE, UL, Class I Division 2 compliant |
| Mounting | Panel cutout mounting for MCC and industrial control cabinet |
| Application | Low and medium voltage three‑phase induction motor protection, widely used in power, petrochemical, water treatment, mining and metallurgical industries |
| Remarks | Obsolete legacy relay; base model of the 269PLUS family, configurable with different RTD types, I/O and power supply variants; fully function tested before shipment; recommended replacement: GE Vernova 859 |

- GE 269-PLUS-D