GE Multilin 369-HI-R-M-F-E-H-E is a discontinued digital motor management relay equipped with 12 built-in programmable RTD inputs, full metering package and optional fiber optic communication port. It supports Modbus TCP Ethernet and multi-serial communication, and is fitted with enhanced diagnostic faceplate. This unit integrates thermal overload, stall, short circuit, ground fault, current unbalance, over / under voltage and frequency protection, together with energy metering, motor start logging and fault oscillography. The fiber interface enables long-distance anti-interference data transmission, widely deployed for medium voltage motor protection inside motor control centers of power, petrochemical, water treatment and metallurgical facilities.

GE 369-HI-R-M-F-E-H-E

Parameter Specification
Product Type Digital motor management & protection relay
Compatible System GE Multilin 369 series motor protection platform
Core Function Motor protection, electrical metering, RTD temperature monitoring, fiber communication, fault recording and control
Signal Type Current / voltage sampling, 12-channel RTD temperature input, digital input, relay output, analog output, fiber optic interface
Galvanic Isolation Galvanic isolation for CT / VT, digital, temperature and fiber communication channels
Power Supply 50–300 VDC / 60–265 VAC
Power Consumption Max 20 VA, peak up to 65 VA
Diagnosis Wire break detection, over-range alarm, built-in self-test, 512 event recorder, oscillography, motor health report
Indicator LED status indicators, backlit LCD with keypad, enhanced diagnostic faceplate
Communication Fiber optic port, Modbus TCP, RS232, multi-channel RS485
Hot Swap Non hot-swappable, panel mounting unit
Operating Temperature -20 ℃ ~ +60 ℃
Storage Temperature -40 ℃ ~ +85 ℃
Humidity 5% ~ 95% non-condensing
Protection Class IP20 for cabinet installation
Certifications CE, UL, Class I Division 2 compliant
Mounting Panel cutout mounting for MCC and control cabinet
Application Medium-sized AC induction motors, two-speed motor protection, suitable for harsh industrial environments in power, oil & gas and process plants
Remarks Obsolete legacy relay with fiber option, fully function tested before shipment; recommended replacement: GE Vernova 859