Description
GE Fanuc IC695ALG708 – RX3i 8-Channel Analog Voltage and Current Output Module

- IC695ALG708
2. Product Overview
The GE Fanuc IC695ALG708 is an 8-channel non-isolated analog output module designed for the PACSystems RX3i PLC platform. It converts digital control values from the PLC into analog voltage or current signals for regulating industrial field devices. Each of its eight channels can be independently configured for voltage or current output, supporting standard ranges such as 0–10 V, ±10 V, 0–20 mA, and 4–20 mA. The module is suitable for controlling devices such as control valves, variable frequency drives, actuators, and other equipment requiring analog reference signals. It features software-based channel configuration, output scaling, alarm limits, configurable output bias, and fault reporting. With an approximately 8 ms update rate across all eight channels, the IC695ALG708 supports responsive analog control in industrial automation applications.
3. Technical Specifications
- Brand: GE Fanuc
- Model: IC695ALG708
- Product Series: PACSystems RX3i
- Product Type: Non-Isolated Analog Output Module
- Number of Channels: 8
- Output Type: Voltage and current
- Voltage Output Ranges: 0–10 V DC, ±10 V DC
- Current Output Ranges: 0–20 mA, 4–20 mA
- Output Resolution:
- ±10 V: 15.9 bits
- 0–10 V: 14.9 bits
- 0–20 mA: 15.9 bits
- 4–20 mA: 15.6 bits
- Output Update Rate: Approximately 8 ms for all eight channels
- Output Data Format: IEEE 32-bit floating point or 16-bit integer in a 32-bit field
- Calibrated Accuracy: ±0.15% of full scale at 25°C; ±0.30% at 60°C
- Maximum Current Output Load: 850 Ω at 20 V external supply
- Minimum Voltage Output Load: 2 kΩ
- Output Settling Time: 2 ms, 0–95%
- Field-to-Backplane Isolation: 2550 V DC for 1 second
- External Power Supply: 19.2–30 V DC
- Maximum Backplane Power Requirement: 375 mA at 3.3 V DC
- Maximum Module Power Dissipation: 7.25 W
- Compatible Platform: RX3i Universal Backplane
- CPU Firmware Requirement: Version 3.0 or later
- Configuration Software: Machine Edition 5.0 SP3 or later
4. Key Features & Benefits
- Eight Configurable Output Channels: Each channel can be configured for voltage or current output to accommodate different field devices.
- Multiple Signal Ranges: Supports standard industrial analog signals, including 4–20 mA and 0–10 V.
- High-Resolution Output: Provides up to 15.9-bit resolution for accurate analog control.
- Fast Output Response: Offers an approximately 8 ms update rate across all eight channels.
- Software-Based Configuration: Supports channel enable or disable, scaling, offsets, output bias, and alarm limits without hardware jumpers.
- Integrated Diagnostics: Provides output fault reporting, alarm monitoring, and configurable output behavior when communication or system faults occur.
5. Application Scenarios
- Process Control Systems: Generates analog signals for regulating control valves, flow controllers, and other process equipment.
- Motor and Drive Control: Provides voltage or current reference signals for variable frequency drives and industrial motor control equipment.
- Manufacturing Automation: Controls actuators and positioning equipment requiring analog command signals.
- Industrial Instrumentation: Interfaces PLC control outputs with field devices using standard 4–20 mA or 0–10 V signals.
6. Frequently Asked Questions
Q1: What is the main function of the IC695ALG708?
It converts digital PLC control values into analog voltage or current signals for industrial field devices.
Q2: How many output channels does the IC695ALG708 provide?
It provides eight independently configurable analog output channels.
Q3: Does the IC695ALG708 support 4–20 mA output?
Yes. It supports both 0–20 mA and 4–20 mA current output ranges.
Q4: Can the module provide voltage output?
Yes. It supports 0–10 V DC and ±10 V DC voltage output ranges.
Q5: Is the IC695ALG708 compatible with the RX3i PLC system?
Yes. It is designed for the PACSystems RX3i platform and installs in an RX3i Universal Backplane.
Q6: Does the module support HART communication?
No. The IC695ALG708 does not support HART. HART functionality is available on the related IC695ALG728 model.