Description
GE IS230STAOH2A
GE IS230STAOH2A is a high‑density isolated analog output terminal board for the Mark VIe PAOC I/O pack. It receives digital setpoint commands from the Mark VIe controller over IONet, converts them into stable 4–20 mA current signals for modulating field control devices such as fuel valves, dampers and variable speed drives. Independent channel isolation eliminates ground loops and cross‑channel interference, while built‑in loop monitoring can detect open or shorted field wiring. This plug‑in board is a standard maintenance spare for Mark VIe turbine, generator and balance‑of‑plant control systems in power generation and oil & gas plants.
GE IS230STAOH2A
| Parameter | Specification |
|---|---|
| Product Type | Analog Output Terminal Board (TAOH) |
| Compatible System | GE Vernova Speedtronic Mark VIe / Mark VIeS, PAOC Analog Output I/O Pack |
| Core Function | Convert digital control commands into isolated 4–20 mA analog output signals, drive modulating field actuators, valve positioners, dampers and VFDs; loop monitoring, surge suppression and signal filtering |
| Signal Type | 16 channels isolated analog output, configurable 4–20 mA / 0–20 mA, 16‑bit DAC resolution |
| Galvanic Isolation | 2500 Vrms channel‑to‑channel and channel‑to‑ground isolation |
| Power Supply | 24 V DC supplied by I/O pack internal backplane |
| Power Consumption | Max 5.2 W |
| Diagnosis | Current loop fault detection, power‑on self‑test, communication heartbeat, over‑range fault flagging |
| Indicator | Module RUN / FAULT LED, channel status indication |
| Communication | IONet deterministic backplane bus, works with Mark VIe distributed I/O packs, supports simplex, dual and TMR redundant configuration |
| Hot Swap | Non hot‑swappable; power off the PAOC I/O pack before replacement |
| Operating Temperature | -30 ℃ ~ +65 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP00 plug‑in circuit board, installed inside control cabinet I/O pack |
| Certifications | UL, CE, Class I Div 2 hazardous location approval, meets power generation SIL requirements |
| Mounting | Plug‑in board for PAOC I/O pack |
| Application | Gas turbine, steam turbine, generator excitation and BoP modulating control in power plants and petrochemical facilities |
| Remarks | Matches with IS220PAOH core analog output pack; fully function tested before shipment |

- IS230STAOH2A