HIMA F3330 | 8-Channel Safety-Related Digital Output Module, In Stock

$658.00

Product Information

Brand: HIMA

Model: F3330

Part Number: F3330

Warranty: 1 year

Quality: Original module

Condition: New

Warehouse: In stock

Delivery time: Shipped in 3-5 days after payment

 

Category: SKU: HIMA F3330 Tag: Brand:
Need This Part? Contact Us Get a quick quote and product availability.
Chat on WhatsApp
Scan to contact Massive PLC on WhatsApp Scan to chat

Description

HIMA F3330 | 8-Channel Safety-Related Digital Output Module, In Stock

Product Overview

The HIMA F3330 is an 8-channel safety-related digital output module designed for HIMA HIQuad H41q and H51q safety control systems. It provides reliable switching of external field devices in safety-critical industrial applications.

The module supports resistive and inductive loads up to 500 mA per channel, with a maximum load rating of 12 W. It also supports lamp connections up to 4 W. Integrated safety shutdown and electrical isolation help protect connected equipment and maintain safe operating conditions.

The F3330 performs automatic online diagnostics, including output signal readback, switching capability testing and cross-talk monitoring. Its short-circuit-protected outputs make it suitable for emergency shutdown systems, process safety applications and industrial automation.

Technical Specifications

Brand: HIMA

Model: F3330

Part Number: F3330

Product Type: Safety-Related Digital Output Module

Product Series: HIQuad H41q / H51q

Number of Outputs: 8

Output Type: Digital transistor output

Nominal Field Supply: 24 VDC

Maximum Output Current: 500 mA per channel

Maximum Load Power: 12 W

Supported Load Types: Resistive and inductive loads

Lamp Connection: Up to 4 W

Output Protection: Short-circuit protected

Internal Voltage Drop: Maximum 2 V at 500 mA load

Maximum Line Resistance: 11 Ω for outgoing and return lines combined

Undervoltage Trip Point: 16 V or lower

Short-Circuit Current Operating Point: 0.75 to 1.5 A

Output Leakage Current: Maximum 350 µA

Output Voltage in Reset State: Maximum 1.5 V

Test Signal Duration: Maximum 200 µs

Diagnostic Functions: Output readback, switching capability testing and cross-talk monitoring

Safety Requirement Class: AK 1 to AK 6

Power Consumption at 5 VDC: 110 mA

Additional Load Consumption at 24 VDC: 180 mA

Rack Space Requirement: 4 TE