Description
1Honeywell TK-FPDXX2
Honeywell TK-FPDXX2 is a field power distribution module for the Honeywell Experion PKS C200 / C300 distributed control system. It accepts a wide range DC input and provides stable 24 VDC power supply with up to 30 A capacity for field instruments and I/O assemblies. It integrates comprehensive hardware protection against short circuit, overload and overheating, and reports diagnostic and fault information to the DCS controller via the rack backplane bus. The module is hot swappable and can be used in redundant power arrangements. It remains a widely stocked maintenance spare for legacy Experion PKS installations in oil refining, chemical and power generation plants.
Honeywell TK-FPDXX2
| Parameter | Specification |
|---|---|
| Product Type | Field Power Distribution Module |
| Compatible System | Honeywell Experion PKS C200 / C300 DCS System |
| Core Function | Regulated 24 VDC field power distribution for field transmitters and I/O modules; provides overcurrent, short-circuit and overtemperature protection, rack power monitoring and fault alarm |
| Signal Type | 19.2–32 VDC input, regulated 24 VDC output, fault alarm contact, internal rack bus interface |
| Galvanic Isolation | Galvanic isolation between field power circuit and DCS internal backplane bus |
| Power Supply | 19.2–32 VDC input |
| Power Consumption | Rated 100 W; derated to 70 W at 60°C, max output current 30 A |
| Diagnosis | Power-on self-test, overvoltage / undervoltage detection, short-circuit lockout, overtemperature monitoring, output current tracking, fault latching |
| Indicator | RUN, OK, FAULT and output status LED indicators |
| Communication | Honeywell proprietary rack control bus for diagnostic upload to controller |
| Hot Swap | Hot swappable; replacement permitted with rack energized |
| Operating Temperature | 0 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 |
| Certifications | UL, CE, CSA certified, conformal coated version available |
| Mounting | Plug-in rack module for Experion PKS chassis |
| Application | Petrochemical, refining and power plant DCS field power supply for HART transmitters and field I/O |
| Remarks | TK-FPDXX2, obsolete legacy spare; supports redundant power configuration; fully function tested before shipment |

- TK-FPDXX2