Description
TRICONEX 2381 PI2381 Pulse Input Baseplate 7400221-100 | Pre-owned Tested
TRICONEX PI2381 (2381, PN:7400221-100) is a triple modular redundancy pulse input baseplate for Trident safety instrumented systems. It provides 8 isolated pulse input channels to receive pulse signals from turbine MPU speed sensors, vortex flow meters and other pulse transmitters. It supports pulse counting and frequency calculation, converts field pulse signals into digital process values for safety logic solver. It adopts TMR fault tolerant voting architecture, single channel failure will not affect safety measurement. Continuous signal diagnosis can detect signal loss and abnormal pulse, and upload fault information to the safety controller. The PCB is conformal coated for anti-corrosion and anti-moisture, suitable for hazardous industrial environments of petrochemical, oil & gas and power plant. It is a core spare component for Trident SIS platform, replacement requires strictly matched firmware and system configuration.
TRICONEX 2381 PI2381 Pulse Input Baseplate 7400221-100 | Pre-owned Tested
| Parameter | Specification |
|---|---|
| Product Type | Pulse Input Module |
| Compatible System | TRICONEX Trident SIS Safety Instrumented System, TMR Safety Control Platform |
| Core Function | 8-channel pulse/frequency signal acquisition, TMR 2oo3 voting processing, speed, flow meter and turbine pulse signal measurement, pulse counting, frequency conversion, signal validation |
| Signal Type | 8 isolated pulse input channels, 0–10kHz frequency range, 5V/24V pulse signal compatible, TriBus backplane interface |
| Galvanic Isolation | Channel-to-backplane reinforced isolation, EMC & surge protection for oil, gas and chemical hazardous zone |
| Power Supply | 24 V DC, 18–32 V DC wide input |
| Power Consumption | Max 10 W |
| Diagnosis | Power-on self-test, watchdog supervision, pulse signal loss detection, channel discrepancy voting fault detection, fault logging & snapshot storage |
| Indicator | Onboard LED for power, pass, active, fault and field alarm |
| Communication | TriBus internal high-speed backplane bus, compatible with TriStation configuration software |
| Hot Swap | Hot swappable in matched Trident rack under redundant configuration |
| Operating Temperature | -20 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% – 95%, non-condensing |
| Protection Class | IP20 when installed inside cabinet |
| Certifications | CE certified, IEC 61508 SIL3 certified |
| Mounting | Plug-in eurocard baseplate for TRICONEX Trident rack |
| Remarks | Model: 2381 / PI2381 / 7400221-100; TMR pulse input baseplate for SIS; conformal coated PCB; firmware version must match Trident system; critical spare for turbine speed and pulse flow monitoring |

- TRICONEX PI2381