Description
TRICONEX DI3301 | 32-Point 24VDC Digital Input Module, Trident Safety Instrumented System Spare Part, In Stock
Model: DI3301
Brand: TRICONEX
Product Type: Digital Input Module
Product Series: Trident Safety Instrumented System
Input Channels: 32 commoned digital input points
Nominal Input Voltage: 24 VDC
Operating Voltage Range: 15–30 VDC
Absolute Maximum Input Voltage: 33 VDC
Maximum Reverse Input Voltage: -0.6 VDC
Input Delay: Less than 10 ms
Time Constant: 6.4 ms, -3 dB at 25 Hz
Input Impedance: Greater than 30 kΩ without baseplate; approximately 3 kΩ with baseplate
Input Power: 0.2 W per point at 24 VDC; 0.5 W per point at 33 VDC
Input Threshold: 0–5 VDC OFF; 6–14 VDC transition; 15–30 VDC ON
Diagnostic Function: Force-to-Value Diagnostics (FVD)
Diagnostic Test Duration: Less than 2 ms per test
Input Scan Time: Less than 1 ms for all 32 points
Functional-to-Protective-Earth Isolation: Minimum 500 VDC
Functional-to-Logic-Earth Isolation: Minimum 800 VDC
System Architecture: Triple Modular Redundancy (TMR)
Application: Emergency shutdown systems, safety interlocks, turbine control, industrial process automation, and digital field signal monitoring
Product Overview
The TRICONEX DI3301 is a 32-point digital input module designed for the Trident safety instrumented system. It receives discrete signals from field devices, such as switches, contacts, alarms, and equipment status indicators, and transfers the input data to the safety controller for processing.
The module uses three independent electronic channels to process input signals and supports redundant safety-system operation. Its built-in Force-to-Value Diagnostics (FVD) continuously checks the input circuits, while the input scanning process reads all 32 points in less than 1 ms.
Operating with nominal 24 VDC field signals, the DI3301 is suitable for industrial applications requiring reliable digital signal acquisition. The module also supports online replacement and hot sparing within compatible Trident system configurations.
The DI3301 is used in industrial safety applications, including emergency shutdown systems, process interlocks, turbine control, and equipment protection. Before ordering, verify the module designation, baseplate compatibility, field wiring configuration, and system revision against the installed equipment documentation.