Description

Woodward 8406-121 – EGCP-2 Engine Generator Control Package

Woodward 8406-121
Woodward 8406-121

 

1. Product Overview

The Woodward 8406-121 is an EGCP-2 Engine Generator Control Package designed to automate and protect diesel and gas engine-driven generator sets. It combines engine management, generator synchronization, real power load control, reactive power control, and protective functions in a single microprocessor-based controller. This model is configured for potential transformer voltage inputs from 50 to 150 VAC RMS, distinguishing it from the 8406-120 version. It supports standalone and utility-paralleled generator operation, as well as coordinated control of multiple generator sets. The front-panel operator interface provides two LCD displays and a membrane keypad for monitoring operating data, alarms, and configuration parameters. With automatic start and stop control, generator sequencing, and Modbus communication, the 8406-121 is suitable for small- and medium-sized industrial power generation systems.

 

2. Technical Specifications

  • Brand: Woodward
  • Model: EGCP-2
  • Part Number: 8406-121
  • Product Type: Engine Generator Control Package
  • Power Supply: 9–32 VDC
  • Nominal Supply Voltage: 12 or 24 VDC
  • Power Consumption: 13 W nominal, 20 W maximum
  • PT Voltage Input: 50–150 VAC RMS
  • CT Current Input: 0–5 A RMS
  • Generator Frequency Range: 40–70 Hz
  • Magnetic Pickup Frequency: 100–10,000 Hz
  • Discrete Inputs: 16
  • Process Input: 4–20 mA or 1–5 VDC
  • Temperature and Pressure Inputs: 0–200 ohm sensors, 4–20 mA transducers, or 0–5 V transducers
  • Speed Bias Output: ±3 VDC, 0.5–4.5 VDC, or 5 V peak PWM at 500 Hz
  • Voltage Bias Output: ±1 VDC, ±3 VDC, or ±9 VDC
  • Relay Outputs: 10 A at 250 VAC resistive or 10 A at 30 VDC resistive
  • Communication Interfaces: RS-485 and RS-422
  • Communication Protocol: Modbus
  • Operator Interface: Two LCD displays and membrane keypad
  • Operating Temperature: -20 to +70 °C
  • Storage Temperature: -40 to +105 °C
  • Humidity: 95% at 20–55 °C
  • Mounting: Front-panel mounting
  • Housing: Sheet-metal enclosure
  • Ingress Protection: IP56 when installed in a suitable enclosure
Woodward 8406-121
Woodward 8406-121

 

3. Key Features & Benefits

  • Integrated Engine Management: Combines engine control, monitoring, and protective functions in one controller.
  • Generator Synchronization: Supports synchronization with other generator sets and utility power systems.
  • Real and Reactive Load Control: Provides kW load management and reactive kVAR control.
  • Automatic Generator Sequencing: Coordinates multiple generator sets for base-load, peak-shaving, and backup power applications.
  • Comprehensive Operator Interface: Two LCD displays and a keypad provide access to operating information, alarms, and configuration settings.
  • Industrial Communication: RS-485 and RS-422 interfaces support Modbus communication with external monitoring and control equipment.

 

4. Application Scenarios

  • Diesel generator control and protection systems.
  • Gas engine-driven generator installations.
  • Industrial power plants with multiple generator sets.
  • Utility-paralleled and standby generator systems.
  • Peak-shaving and base-load power generation applications.

 

5. Frequently Asked Questions

Q1: What is the Woodward 8406-121?

It is an EGCP-2 Engine Generator Control Package used for engine management, generator synchronization, load control, and protection.

Q2: What is the PT voltage input range?

The 8406-121 supports a potential transformer input range of 50–150 VAC RMS.

Q3: What power supply does this controller require?

It operates on a 9–32 VDC supply and supports nominal 12 VDC or 24 VDC systems.

Q4: Can the 8406-121 control multiple generator sets?

Yes. A network of EGCP-2 controllers can coordinate up to eight generator sets.

Q5: Which communication interfaces are available?

It provides RS-485 and RS-422 interfaces and supports Modbus communication.

Q6: Is the 8406-121 suitable for hazardous locations?

No. The EGCP-2 is specified for use in non-hazardous locations.