Description
EPRO MMS6312 | Monitoring Module MMS 6312
EPRO MMS6312 is a dual‑channel speed and keyphase monitor module within the Emerson MMS6000 machinery protection system. It accepts signals from eddy‑current probes and pulse sensors for continuous measurement of shaft rotational speed, zero speed, keyphase trigger pulses, rotation direction and speed difference. Each channel can be configured independently, and the module provides isolated analog output, TTL pulse output and configurable alarm relays for overspeed and abnormal operating conditions. Built‑in diagnostics detect sensor failures and abnormal signals, and all measurement parameters are protected by password. Serial ports support local configuration and data uploading to DCS or monitoring host. This module is critical for turbine overspeed protection; original manufacturing has been discontinued, and replacement requires identical model and compatible project configuration.
EPRO MMS6312 | Monitoring Module MMS 6312
| Parameter | Specification |
|---|---|
| Product Type | Dual‑Channel Rotational Speed / Keyphase Monitoring Module |
| Compatible System | EPRO MMS 6000 Machinery Monitoring System (Emerson) |
| Core Function | Independent dual‑channel speed and keyphase measurement; monitors shaft rotating speed, zero speed, keyphase pulse, rotation direction and speed differential; supports adjustable pre‑alarm and danger alarm relays, overspeed protection, run‑down detection and sensor diagnostics |
| Signal Type | Eddy‑current / pulse sensor input (PR6422, PR6425, PR9376, PR6453), keyphase input, 4–20 mA analog output, TTL pulse output, alarm relay contacts, RS232 / RS485 configuration port |
| Galvanic Isolation | Galvanic separation for sensor circuits, relay outputs and backplane; conforms to EN 50081‑1, EN 50082‑2 EMC requirements |
| Power Supply | 18–31.2 V DC, redundant power support |
| Power Consumption | Max 6 W |
| Diagnosis | Power‑on self‑test, sensor cable break / short‑circuit detection, signal plausibility check, watchdog supervision, password protected parameter setup |
| Indicator | RUN, FAULT, PRE‑ALARM, DANGER and per‑channel status LED indicators on front plate |
| Communication | RS232, RS485 for configuration and measured value transmission |
| Hot Swap | Non hot‑swappable; rack power must be de‑energized before replacement |
| Operating Temperature | 0 ℃ ~ +65 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95%, non‑condensing |
| Protection Class | Module IP00, front panel IP21 |
| Certifications | CE, IEC 61000, IEC 68‑2 |
| Mounting | Eurocard DIN 41494, 6 TE / 3 HE plug‑in module for MMS6000 rack |
| Application | Steam turbine, gas turbine, compressor, fan and generator; overspeed and keyphase protection in power, petrochemical and metallurgical plants |
| Remarks | MMS6312; measuring frequency range up to 20 kHz, maximum measurable speed 65535 RPM; widely paired with eddy current probes and preamplifier CON011; original production discontinued, supplied as aftermarket spare parts; firmware and configuration must match existing MMS6000 rack |

- MMS6312