Description
GE 369-HI-R-M-0-0-0-E
GE Multilin 369-HI-R-M-0-0-0-E is a discontinued digital motor management relay equipped with full metering package and 12 programmable RTD inputs, standard enhanced faceplate without conformal coating. It supports RS485 Modbus RTU and RS232 communication, no onboard Ethernet or fiber interface. This unit integrates thermal overload, stall, short circuit, ground fault, current unbalance, over / under voltage and frequency protection, energy metering, motor start logging and fault oscillography. It is widely deployed for medium voltage motor protection inside motor control centers of power, petrochemical, water treatment and metallurgical facilities under normal environmental conditions.
GE 369-HI-R-M-0-0-0-E
| Parameter | Specification |
|---|---|
| Product Type | Digital motor management & protection relay |
| Compatible System | GE Multilin 369 series motor protection platform |
| Core Function | Motor protection, electrical metering, 12‑channel RTD temperature monitoring, fault recording and control |
| Signal Type | Current / voltage sampling, 12‑channel RTD temperature input, 6 optically isolated digital inputs, relay outputs, 4 programmable analog outputs |
| Galvanic Isolation | Galvanic isolation for CT / VT, digital and temperature channels |
| Power Supply | 50–300 VDC / 60–265 VAC |
| Power Consumption | Max 20 VA, peak up to 65 VA |
| Diagnosis | Wire break detection, over‑range alarm, built‑in self‑test, 512 event recorder, oscillography, motor health report |
| Indicator | LED status indicators, backlit LCD with keypad, standard enhanced diagnostic faceplate (non‑coated) |
| Communication | RS232 front port, three rear RS485 ports, Modbus RTU (without Ethernet or fiber optic port) |
| Hot Swap | Non hot‑swappable, panel mounting unit |
| Operating Temperature | -20 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 for cabinet installation |
| Certifications | CE, UL, Class I Division 2 compliant |
| Mounting | Panel cutout mounting for MCC and control cabinet |
| Application | Medium‑sized AC induction motors, two‑speed motor protection for standard industrial environments in power, oil & gas and process plants |
| Remarks | Obsolete legacy relay, standard version without conformal coating; fully function tested before shipment; recommended replacement: GE Vernova 859 |

- GE 369-HI-R-M-0-0-0-E