Description
GE Multilin 369 – HI-R-M-O-E-O-E
GE Multilin 369‑HI‑R‑M‑O‑E‑O‑E is a high‑spec variant of the classic 369 motor management relay. This version includes the high auxiliary power supply, 12 built‑in RTD channels for winding and bearing temperature monitoring, the full metering suite with four analog outputs, Modbus TCP Ethernet, plus the enhanced front panel with advanced diagnostics and motor health logging. It learns the thermal and starting profile of each individual motor and provides flexible overload curves, stall protection and fault waveform capture for post‑trip analysis. Configuration and data retrieval are carried out via EnerVista software. Now end‑of‑production, it is supplied primarily as critical spare for existing installed motor protection fleets.
GE Multilin 369 – HI-R-M-O-E-O-E
| Parameter | Specification |
|---|---|
| Product Type | Full‑feature numerical motor management & protection relay |
| Compatible System | MV / LV three‑phase induction motors, pumps, fans, compressors, crushers and variable‑frequency driven motors |
| Order Code Breakdown | HI: High auxiliary supply (50–300 V DC / 60–265 V AC); R: 12‑channel built‑in RTD input; M: Full metering package with 4 analog outputs; O: No fiber port; E: Modbus TCP Ethernet communication; O: No harsh‑environment conformal coating; E: Enhanced faceplate plus advanced diagnostics & motor health reporting |
| Rated Frequency | 50 / 60 Hz selectable |
| CT Secondary | 1 A / 5 A software selectable |
| Auxiliary Supply | 50–300 V DC / 60–265 V AC |
| Core Protection Functions | Adaptive thermal overload, locked rotor, stall / jam protection, start supervision, multi‑stage overcurrent, short‑circuit, earth fault, negative sequence current unbalance, phase loss, phase reversal, undercurrent, overvoltage / undervoltage, RTD stator / bearing temperature protection, breaker failure protection, trip circuit supervision |
| Metering Package | Current, line voltage, active / reactive / apparent power, power factor, frequency, energy, demand, RTD temperature readings |
| Recording | Time‑stamped event log, fault oscillography, motor start data logger, motor health report, security audit trail |
| Communication | Front RS232 service port, rear RS485 Modbus RTU, embedded Ethernet Modbus TCP |
| Local Interface | Enhanced backlit graphic LCD, membrane keypad, dedicated status LEDs, configurable digital inputs and programmable relay outputs |
| Diagnosis | Continuous self‑supervision, RTD open / short detection, trip circuit supervision, watchdog monitoring, learned motor characteristic alarm |
| Mounting | Panel flush mounting, withdrawable plug‑in unit |
| Operating Temperature | -40 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP54 front panel, IP20 rear terminal compartment |
| Certifications | CE, UL, CSA |
| Application | Petrochemical, mining, power plant, water treatment, offshore platform critical motor protection, two‑speed motors and VFD‑fed motor supervision |
| Remarks | Discontinued legacy Multilin relay; fully calibrated, firmware loaded, protection elements and Ethernet communication verified before shipment |

- GE Multilin 369 – HI-R-M-O-E-O-E