GE MULTILIN 369 369-HI-R-M-0-0-H
GE Multilin 369-HI-R-B-F-E-H-E is a discontinued digital motor management relay equipped with back-spin detection function and 12 programmable RTD inputs, excluding the full metering package and analog output. It is fitted with fiber optic communication port and enhanced diagnostic faceplate with harsh‑environment conformal coating, supporting Modbus TCP over fiber, RS485 Modbus RTU and RS232 communication. This unit integrates thermal overload, stall, short circuit, ground fault, current unbalance, over / under voltage and frequency protection, together with fault oscillography and motor start logging. The back-spin detection is specially designed for down‑hole pumps, while the conformal coating and fiber interface make it suitable for offshore, humid and corrosive working conditions in petrochemical and oilfield facilities.
GE MULTILIN 369 369-HI-R-M-0-0-H
| Parameter | Specification |
|---|---|
| Product Type | Digital motor management & protection relay |
| Compatible System | GE Multilin 369 series motor protection platform |
| Core Function | Motor basic protection, back-spin detection, 12‑channel RTD temperature monitoring, fiber communication, fault recording and control (without full metering package) |
| Signal Type | Current / voltage sampling, 12‑channel RTD temperature input, 6 optically isolated digital inputs, relay outputs, fiber optic communication channel, no analog output |
| Galvanic Isolation | Galvanic isolation for CT / VT, digital, temperature and fiber communication channels |
| Power Supply | 50–300 VDC / 60–265 VAC |
| Power Consumption | Max 20 VA, peak up to 65 VA |
| Diagnosis | Wire break detection, over‑range alarm, built‑in self‑test, 512 event recorder, oscillography, motor start logger |
| Indicator | LED status indicators, backlit LCD with keypad, conformal coated harsh environment faceplate |
| Communication | Fiber optic port, Modbus TCP, RS232 front port, three rear RS485 ports, Modbus RTU |
| Hot Swap | Non hot‑swappable, panel mounting unit |
| Operating Temperature | -20 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 for cabinet installation |
| Certifications | CE, UL, Class I Division 2 compliant |
| Mounting | Panel cutout mounting for MCC and control cabinet |
| Application | Medium‑sized AC induction motors, submersible down‑hole pump motor protection, harsh corrosive industrial environments in oil & gas, offshore and process plants |
| Remarks | Obsolete legacy relay, B = Back‑spin detection option, no M metering package, fiber communication + harsh environment conformal coating; fully function tested before shipment; recommended replacement: GE Vernova 859 |

- GE MULTILIN 369 369-HI-R-M-0-0-H