Description
GE Multilin 369-HI-0-0-0-0-0-E
GE Multilin 369-HI-0-0-0-0-0-E is a discontinued base-model digital motor management relay with enhanced diagnostic faceplate. It excludes RTD temperature monitoring, full metering package, back-spin detection, fiber and Ethernet communication modules, supporting only RS485 Modbus RTU and RS232 communication. This relay integrates thermal overload, stall, short circuit, ground fault, current unbalance, over / under voltage and frequency protection, fault oscillography, motor start logging and built-in motor health report. It is used for medium voltage motor protection in ordinary control cabinets of power plants, petrochemical, water treatment and metallurgical facilities, for scenarios where temperature monitoring, energy metering and high-speed network communication are not required.
GE Multilin 369-HI-0-0-0-0-0-E
| Parameter | Specification |
|---|---|
| Product Type | Digital motor management & protection relay |
| Compatible System | GE Multilin 369 series motor protection platform |
| Core Function | Basic motor protection, fault recording and control; no RTD inputs, no metering package, no back‑spin detection, no fiber / Ethernet communication |
| Signal Type | Current / voltage sampling, 6 optically isolated digital inputs, relay outputs, only one native analog output |
| Galvanic Isolation | Galvanic isolation for CT / VT and digital channels |
| Power Supply | 50–300 VDC / 60–265 VAC |
| Power Consumption | Max 20 VA, peak up to 65 VA |
| Diagnosis | Wire break detection, over‑range alarm, built‑in self‑test, 512 event recorder, oscillography, dedicated motor health report |
| Indicator | LED status indicators, backlit LCD with keypad, enhanced diagnostic faceplate, non‑coated standard version |
| Communication | RS232 front port, three rear RS485 ports, Modbus RTU; no onboard Ethernet, fiber, DeviceNet or Profibus |
| Hot Swap | Non hot‑swappable, panel mounting unit |
| Operating Temperature | -20 ℃ ~ +60 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95% non‑condensing |
| Protection Class | IP20 for cabinet installation |
| Certifications | CE, UL, Class I Division 2 compliant |
| Mounting | Panel cutout mounting for MCC and control cabinet |
| Application | Medium‑sized AC induction motors, two‑speed motor protection for standard industrial environments that only require fundamental motor protection functions |
| Remarks | Obsolete legacy relay; base unit without RTD, metering, back‑spin and special communication options, equipped with enhanced diagnostic faceplate, no harsh‑environment conformal coating; fully function tested before shipment; recommended replacement: GE Vernova 859 |

- GE Multilin 369-HI-0-0-0-0-0-E