Description
Woodward 9907-164 505E Steam Turbine Speed Governor | Used Working Pull
Woodward 9907-164 is the 24VDC low voltage version of the 505E digital governor, designed for extraction / admission steam turbine control in power generation and process plants. Built on 32-bit microprocessor architecture, it executes precise speed regulation, load control and extraction pressure closed-loop control. It accepts dual magnetic pickup speed signals, supports remote setpoint via analog channels and communicates with DCS through Modbus RTU. It integrates comprehensive alarm, trip logging and trend recording functions for turbine protection and troubleshooting. It is equipped with front keypad and LCD display for local configuration and monitoring. It is a critical aftermarket spare for steam turbine control systems; commissioning requires application-specific turbine configuration and parameter tuning.
Woodward 9907-164 505E Steam Turbine Speed Governor | Used Working Pull
| Parameter | Specification |
|---|---|
| Product Type | 505E Digital Turbine Governor Controller |
| Compatible System | Single extraction / extraction-admission Steam Turbine |
| Core Function | Turbine speed governing, load control, extraction pressure regulation, start-up ramp control, overspeed alarm & trip logic, fault event recording |
| Signal Type | Dual MPU speed inputs, 4-20mA analog inputs, 4-20mA analog outputs, discrete digital I/O, relay trip outputs |
| Galvanic Isolation | Isolated analog channels, isolated communication port, surge protection for field wiring |
| Power Supply | 24 V DC, 18–32 V DC wide input |
| Power Consumption | Max 45 W |
| Diagnosis | Speed loss detection, actuator fault, supply voltage monitoring, configuration checksum error, trip event snapshot & historical log |
| Indicator | LCD display + LED status indicators for run, alarm, trip |
| Communication | RS485 Modbus RTU |
| Hot Swap | Not hot swappable |
| Operating Temperature | -20 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Humidity | 5% ~ 95%, non-condensing |
| Protection Class | NEMA4 front panel, IP20 for rear terminal section |
| Certifications | CE, cUL, CSA certified |
| Mounting | Panel mount cutout installation for control cabinet |
| Remarks | 9907-164, 505E 24VDC low voltage model; different from 9907-162 (180–264VAC), 9907-163 (88-132VAC/90-150VDC); requires matching turbine application configuration file; widely used in paper mill, chemical plant and power station steam turbines |